Siemens 6ES7132-6BF00-0BA0
*** Spare part *** SIMATIC ET 200SP, digital output module, DQ 8x 24 V DC/0.5 A Standard, suitable for BU type A0, color code CC02, module diagnostics
Data sheet 6ES7132-6BF00-0BA0
SIMATIC ET 200SP, DIGITAL OUTPUT MODULE, DQ
8X24VDC/0,5A STANDARD, FITS TO BU-TYPE A0, COLOR CODE
CC02, MODULE DIAGNOSIS
General information
Product type designation ET 200SP, DQ 8x 24 V DC/0.5 A ST, PU 1
Firmware version V1.1
● FW update possible Yes
usable BaseUnits BU type A0
Color code for module-specific color identification
plate
CC02
Product function
● I&M data Yes; I&M0 to I&M3
Engineering with
● STEP 7 TIA Portal configurable/integrated as of
version
V11 SP2 / V13
● STEP 7 configurable/integrated as of version V5.5 SP3 / -
● PCS 7 configurable/integrated as of version V8.1 SP1
● PROFIBUS as of GSD version/GSD revision GSD Revision 5
● PROFINET as of GSD version/GSD revision GSDML V2.3
Operating mode
● DQ Yes
● DQ with energy-saving function No
6ES7132-6BF00-0BA0 Subject to change without notice
Page 1/4 12/23/2016 © Copyright Siemens AG
● PWM No
● Oversampling No
● MSO No
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 35 mA; without load
Output voltage
Rated value (DC) 24 V
Power loss
Power loss, typ. 1 W
Address area
Address space per module
● Address space per module, max. 1 byte; + 1 byte for QI information
Hardware configuration
Automatic encoding
● Mechanical coding element Yes
Selection of BaseUnit for connection variants
● 1-wire connection BU type A0
● 2-wire connection BU type A0
● 3-wire connection BU type A0 with AUX terminals
● 4-wire connection No
Digital outputs
Number of digital outputs 8
Current-sinking No
Current-sourcing Yes
Short-circuit protection Yes
● Response threshold, typ. 0.7 to 1.3 A
Limitation of inductive shutdown voltage to Typ. L+ (-50 V)
Controlling a digital input Yes
Switching capacity of the outputs
● with resistive load, max. 0.5 A
● on lamp load, max. 5 W
Load resistance range
● lower limit 48 Ω
● upper limit 12 kΩ
Output current
6ES7132-6BF00-0BA0 Subject to change without notice
Page 2/4 12/23/2016 © Copyright Siemens AG
● for signal "1" rated value 0.5 A
● for signal "0" residual current, max. 0.1 mA
Output delay with resistive load
● "0" to "1", max. 50 μs; at rated load
● "1" to "0", max. 100 μs; at rated load
Parallel switching of two outputs
● for uprating No
Switching frequency
● with resistive load, max. 100 Hz
● with inductive load, max. 2 Hz
● on lamp load, max. 10 Hz
Total current of the outputs
● Current per channel, max. 0.5 A
● Current per module, max. 4 A
Total current of the outputs (per module)
horizontal installation
— up to 60 °C, max. 4 A
vertical installation
— up to 50 °C, max. 4 A
Cable length
● shielded, max. 1 000 m
● unshielded, max. 600 m
Isochronous mode
Isochronous operation (application synchronized up
to terminal)
No
Interrupts/diagnostics/status information
Diagnostics function Yes
Substitute values connectable Yes
Alarms
● Diagnostic alarm Yes
Diagnostic messages
● Monitoring the supply voltage Yes
● Wire-break Yes; Module-wise
● Short-circuit Yes; Module-wise
● Group error Yes
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
● Channel status display Yes; Green LED
● for channel diagnostics No
● for module diagnostics Yes; green/red DIAG LED
Potential separation
6ES7132-6BF00-0BA0 Subject to change without notice
Page 3/4 12/23/2016 © Copyright Siemens AG
Potential separation channels
● between the channels No
● between the channels and backplane bus Yes
Isolation
Isolation tested with 707 V DC (type test)
Dimensions
Width 15 mm
Height 73 mm
Depth 58 mm
Weights
Weight, approx. 28 g
last modified: 12/22/2016
6ES7132-6BF00-0BA0 Subject to change without notice